Navin's WSS Towers
IT Park
Main Main
Classification : I T - I T E S Space
Type : Lease/Rental/Sale - Office Space
Address :


No.107&108,Harris Road,
1,2,3,4 Langs Garden Road,
Chennai-600 002

Carpet Area Sizes : 8440 Sqft
Status : Completed
Picture Gallery

Ideal for Software /IT office space in the Nerve centre of Chennai ‘s CBD off Mount Road on Harris Road & Langs Garden Road. Easy access from both Mount Road & Poonamallee High Road.

  • Plumbing/Sanitary:Water requirements designed @ 45 liters per day per head
  • Parry ware/Hindustan White Sanitary Ware.
  • Jaguar Chronium Plated Continental Range Fittings.
  • Separate Toilet for Physically Challenged.
  • Sullage Treatment plant–for use of recycled water for flushing/gardening.
  • Fire Fighting:Modern Automatic System strictly conforming to NBC 2005.
  • Full Fledged Hydrant System–Wet Risers to cover entire floor of the Building.
  • First Aid Hose Reel,Landing Valves/CP Hoses at each floor.
  • Ring Main around the building with additional Fire Brigade inlets for external source of fire protection.
  • 100% Backup Pumping Units on alternate power source with motor control and center panels and individual panels for diesel and jockey pumps.Automatic Sprinkler System for ground/Stilt floor with Dedicated Pumping Units and with 100% backup.
  • Early warning microprocessor Detection System with individual control panel with imported Edwards system panel.
  • Automatic Sprinklers provided in all floors.
  • Air Conditioning:Fully air conditioned office space.
  • TOTAL LOAD-280.5TR
  • FOR 1ST FLOOR-33.0 TR
  • 2 TO 10 TH FLOOR-27.50 TR.
  • DG for 100% back up including for Air Conditioning.
  • Electrical Lighting:Design connected lighting load of 10KW per floor.Design lighting level–300 LUX.
  • Designed for LT power supply & provision given for upgrading to HT supply if block booking of at least five floors is made by a single client.
  • Distribution cable from EB room to individual plate provided.All internal office cabling & switches are under client’s scope.
  • Only shaft provision given.Distribution/Cabling are under client’s scope.
  • UPS:Centralized Location of UPS possible for each floor plate.
  • UPS shaft provided.
  • Total Load includes provision for ups for Data Room.
  • Common Services: Common Area lighting, Car Park lighting, Lifts, Water & fire fighting pumps & Sewage Treatment Plant etc., provided sufficient capacitor for APFC power factor compensation for the reactive loads provided. Any extra compensation required at each floor level is not covered.
  • EB Supply:The total connected load 1230 KVA approx( including Common Area)
  • Active Load:1075 approx ( @ 96 KVA per floor floor plate)
  • Transformer capacity:1000 KVA ( 2 X 500 KVA )
  • DG:100% backup including for air conditioning.
  • FOR FLOOR LOADS-2 X 500KVA
  • FOR COMMON LOAD-1 X 380KVA
  • Lifts:3nos.Automated High speed Lifts of premium make
  • RCC Framed Structure on Pile Foundations
  • Designed for Seismic Zone 1 1 1–safe against earthquakes
  • Post Tensioned Flat Slabs–No beams and hence large floor clearances
  • 10 meter clear column Grids with large column free spaces
  • Individual Floor Height–3300mm roof slab to roof slab
  • Large Areas of Glass Facades–Imposing Elevation
  • Granite/Marble/Vitrified Tile Flooring in Lobbies and Staircases
  • Granite/Marble Cladding for lift facia in lobbies